Try searching by key words, order- or product code or serial number e.g. “CM442” or “Technical information”
Enter at least 2 characters to start the search.
Product picture of: Deltabar S FMD76

Deltabar S FMD76

FMD76
Please Wait (spinning wheel)
Loading price
Prices temporarily unavailable
Price on request
activating price
price: provide information
from CHF ??.-
Filter Measuring / Application task
Measuring / Application task
  • Characteristic

    Digital transmitter with ceramic measuring diaphragms
    Modular transmitter
    Long-term stability
    Enhanced safety via self diagnostic functions
    High resistance to abrasion
    Secondary process barrier

  • Supply voltage

    4...20mA HART:
    10,5...45V DC
    Ex ia: 10,5...30V DC
    PROFIBUS PA /
    FOUNDATION Fieldbus:
    9...32V DC

  • Reference Accuracy

    0,075%
    "PLATINUM" 0,05%

  • Long term stability

    0,05% of URL/year
    0,125% of URL/5 years

  • Process temperature

    -20°C...85°C
    (-4°F...185°F)

  • Ambient temperature

    -20°C...85°C
    (-4°F...185°F)

  • Measuring cell

    100mbar...3bar
    (40inH2O...45psi)

  • Max. overpressure limit

    on one side:
    100 bar
    (1500psi)

  • Process connection

    1/4-18NPT
    RC1/4"
    Flanges (DIN, ASME, JIS)

  • Communication

    4...20mA HART
    PROFIBUS PA
    FOUNDATION Fieldbus

  • Certificates / Approvals

    ATEX
    FM
    CSA
    NEPSI
    IECEx

  • Safety approvals

    SIL
    WHG/ Overfill prevention

  • Design approvals

    EN10204-3.1

  • Marine approvals

    GL

  • Specialities

    diagnostic functions

  • Successor

    No direct successor. According to application FMD77 or PMC71.

  • Characteristic / Application

    Digital transmitter with ceramic measuring diaphragms
    Modular transmitter
    Long term stability
    Enhanced safety via self diagnostic functions
    High resistance to abrasion
    Secondary process barrier

  • Supply / Communication

    4...20 mA HART:
    10,5...45V DC
    Ex ia: 10,5...30V DC
    PROFIBUS PA /
    FOUNDATION Fieldbus:
    9...32V DC

  • Accuracy

    0,075%
    "PLATINUM" 0,05%

  • Long term stability

    0,05% of URL/year

  • Ambient temperature

    -20°C...85°C
    (-4°F...185°F)

  • Process temperature

    -20°C...85°C
    (-4°F...185°F)

  • Process pressure / max. overpressure limit

    100bar (1500psi)

  • Pressure measuring range

    100mbar...3bar
    (1.5psi...45 psi)

  • Main wetted parts

    Ceramic
    Alloy C276
    316L
    Monel
    Tantalum

  • Process connection

    1/4-18NPT
    RC1/4"
    Flanges (DIN, ASME, JIS)

  • Max. measurement distance

    30m (98ft) H2O

  • Communication

    4...20 mA HART
    PROFIBUS PA
    FOUNDATION Fieldbus

  • Certificates / Approvals

    ATEX
    FM
    CSA
    NEPSI
    IECEx
    SIL
    GL marine
    WHG/ Overfill prevention
    EN10204-3.1

  • Options

    HistoROM/M-Dat
    4-line digital display
    SS- or Aluminiumhousing
    Separate housing

  • Successor

    No direct successor. According to application FMD77 or PMC71.

  • Application limits

    Measuring cell: